Qtech-data-systems Q71 External 1200bps Modem User Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
Q71B–QuickStartGuide–v1.1–April2013
www.qtech.co.nz Tel:033663713
Configuration
TheDATRANIIeXcelmustbeconfiguredsothatitwillusetheQ71Bforcommunications.
PoweruptheRTUandconnectQ90softwaretotheRTU.
Navigatetothe“Communications”tabandset“DeviceType”asshownbelow.
TheupperRS232portisconfiguredinthesameway.
Q03RTUConfiguration XL4RTUConfiguration
Diagnostics
TheQ71BhasthreestatusLEDs.
PWR–Power.GreenLEDisonwhenpowerisapplied.
RX–Receive.OrangeLEDinonwhenradiomuteisactive.
TX–Transmit.OrangeLEDisonwhenRTUistransmitting.
IftheGreenPWRLEDisnotoncheckthefuse.
Tuning
Q03RTUTuning
OncetheQ03DhasbeenconfiguredtousetheQ71B,thetransmitaudiosignallevelcan
be adjusted by pressing the Set TX Level” button in Q90. This will make the Q71B
transmitacontinuoustone,andanACvoltagemetercanbeplacedacrossthepinsofthe
connectorlabelled“LVL”intheQ71B.
Turnthepotentiometeranti-clockwisetoreducethesignallevel
Turnthepotentiometerclockwisetoincreasethesignallevel
Note–thisprocesswillhavealreadybeenperformedaspartofthefactorysetupatQTech
priortodelivery.Thedefaultlevelis-3dBm(548mV)intoa600resistiveload.
XL4RTUTuning
ThisisperformedinaverysimilarmethodtotheaboveQ03processbutviaWorkbench.
Page view 3
1 2 3 4

Comments to this Manuals

No comments